| 技术规格 (32节电池)Technical specification(三进三出): |
| 10KVA-80KVA |
| 型号 |
MD-C10K |
MD-C15K |
MD-C20K |
MD-C30K |
MD-C40K |
MD-C60K |
MD-C80K |
| 3/3L |
3/3L |
3/3L |
3/3L |
3/3L |
3/3L |
3/3L |
| 额定功率(W) |
10KVA/ |
15KVA/ |
20KVA/ |
30KVA/ |
40KVA/ |
60KVA/ |
80KVA/ |
| 8KW |
12KW |
16KW |
24KW |
32KW |
48KW |
64KW |
| 效率 |
>85% |
>90% |
| 电池电压 |
384VDC |
| 环 |
可闻噪音 |
<58dB |
<63dB |
| 境 |
| 尺寸 |
600×550×1250 |
720×670×1450 |
| W×D×H(mm) |
| 重量(kg) |
200/230 |
230/265 |
270/305 |
330/365 |
360/560 |
430/480 |
500/550 |
| 100KVA-400KVA |
| 型号 |
MD-C100K |
MD-C120K |
MD-C150K |
MD-C200K |
MD-C300K |
MD-C400K |
| 3/3L |
3/3L |
3/3L |
3/3L |
3/3L |
3/3L |
| 额定功率(W) |
100KVA/ |
120KVA/ |
150KVA/ |
200KVA/ |
300KVA/ |
400KVA/ |
| 80KW |
96KW |
120KW |
160KW |
240KW |
320KW |
| 效率 |
>93 |
>94 |
| 电池电压 |
384VDC |
396VDC |
408VDC |
| 环境 |
可闻噪音 |
<65dB |
<68dB |
| 尺寸W×D×H(mm) |
1000×900×1680 |
1600×980×1800 |
| 重量(kg) |
780/840 |
880/940 |
950/1010 |
1600/1700 |
2100/2200 |
2500/2600 |
| 通用参数 |
| UPS输入 |
电压 |
三相四线380V/400V/415V±20% |
| 频率 |
50Hz±10%/60Hz±10% |
| UPS输出 |
电压 |
三相四线制380V/400V/415V±1%( 静态) 380V/400V/415V±3%(负载0~100%变化) |
| 频率 |
50Hz±0.05%/60Hz±0.05%(本机振荡器) 与市电输入同步(市电时) |
| 过载能力 |
130%时10分钟;130-150%时60秒 |
| 波峰因子 |
03:01 |
| 失真度 |
相电压总谐波失真度<3%(100%线性负载) |
| 输出波形 |
纯正弦波 |
| 100%负载不平衡 |
连续运行 |
| 功率因数 |
0.8-1滞后 |
| 转换时间 |
市电旁路→逆变器0ms 逆变器→ 市电旁路<1ms |
| 短路 |
输出关闭,不跳旁路 |
| 电池 |
充电电流 |
6-20A |
| 显示 |
LCD |
大屏点阵显示运行状态、菜单操作、电压、电池、参数、机型等 |
| LED |
UPS 运行、市电异常、UPS 故障 |
| 接口 |
通讯接口 |
真正RS232接口 |
| 环境 |
温度、湿度 |
0-40℃、90% |
| 备注 |
规格变更恕不另行通知 |
| 本公司接受特殊规格产品的订做 |
|